Heat Shrinkable Heavy Wall Tubing upto 66 kV

Heat Shrinkable Heavy Wall Tubing upto 66 kV

Enquire Now

Features

  • Halogen Free
  • Suitable for underground buried conditions
  • Continuous operation temperature: -40 C to 125 C
  • Meets the requirements of ESI 09 13
  • Shrink Temperature: 120 C
  • Unlimited shelf life and Flame retardant
Heat Shrinkable Heavy Wall Tubing upto 66 kV

Specifications

Dimension Chart for Heat Shrink Heavy Wall Tubing

Code Diameter
As Supplied (mm)
Diameter
After Recovered (mm)
Recovered Wall
Thickness (mm)
DTSR - ø9/3 9 3 1.8
DTSR - ø13/4 13 4 2.4
DTSR - ø22/6 22 6 2.7
DTSR - ø33/8 33 8 3.2
DTSR - ø40/12 40 12 4.1
DTSR - ø45/12 45 12 4.1
DTSR - ø55/16 55 16 4.1
DTSR - ø75/22 75 22 4.1
DTSR - ø85/25 85 25 4.1
DTSR - ø95/29 95 29 4.1
DTSR - ø115/34 115 34 4.3
DTSR - ø130/36 130 36 36
DTSR - ø160/50 160 50 4.3
DTSR - ø180/50 180 50 4.3
DTSR - ø200/60 200 60 4.3
Note: All dimensions are in mm

Technical Data for Heat Shrink Heavy Wall Tubing

Property Requirements Test Method
Physical
Specific Gravity 1.10 ASTM D 1505 / ISO 1183
Tensile Strength 10 N/mm (min.) ASTM D 412 / ISO 37
Ultimate Elongation 200% (min.) ASTM D 412 / ISO 37
Water Absorption (25 C) 0.5% (max.) ASTM D 570
Thermal Ageing
Continuous Operating Temperature -55 C to +130 C IEC 216
Shrink Temperature 120 C (min.) IEC 216
Heat Shock (30 min. 200 C) No cracking / No flowing
Heat Ageing (168 hrs 120 C)
Tensile Strength 7.0 N/mm (min.) ASTM D 412 / ISO 37
Ultimate Elongation 100% (min.)
Low Temperature Flexibility (-20 C) No cracking ASTM D 2671
Electrical
Dielectric Strength 10 kV/mm (min.) ASTM D 149 / IEC 243
Volume Resistivity 1 x 10" 2 cm (min.) ASTM D 257 / IEC 93