Accessories
Features
- Anti-tracking
- Light Weight
- Superior UV and Abrasion Resistance
- Weather Resistance
- Range Taking
- Quick Installation
- Localized Installation
Specifications:
Dimension Chart for Silicone Conductor Cover for 11 kV
Suitable Conductor Selection mm2 |
Size - ø D (mm) |
Thickness - A (mm) |
25-50 |
ø12 |
2 |
70-95 |
ø15 |
2 |
120-150 |
ø20 |
2 |
185-240 |
ø25 |
2 |
300-400 |
ø30 |
2 |
500 |
ø35 |
2 |
Dimension Chart for Silicone Conductor Cover for 35 kV
Suitable Conductor Selection mm2 |
Size - ø D (mm) |
Thickness - A (mm) |
25-50 |
ø12 |
3 |
70-95 |
ø15 |
3 |
120-150 |
ø20 |
3 |
185-240 |
ø25 |
3 |
300-400 |
ø30 |
3 |
500 |
ø35 |
3 |
Dimension Chart for Silicone Conductor Cover for 110 kV
Suitable Conductor Selection mm2 |
Size - ø D (mm) |
Thickness - A (mm) |
25-50 |
ø12 |
5 |
70-95 |
ø15 |
5 |
120-150 |
ø20 |
5 |
185-240 |
ø25 |
5 |
300-400 |
ø30 |
5 |
500 |
ø35 |
5 |
Dimension Chart for Silicone Conductor Cover for 220 kV
Suitable Conductor Selection mm2 |
Size - ø D (mm) |
Thickness - A (mm) |
25-50 |
ø12 |
8 |
70-95 |
ø15 |
8 |
120-150 |
ø20 |
8 |
185-240 |
ø25 |
8 |
300-400 |
ø30 |
8 |
500 |
ø35 |
8 |
Technical Data for Silicon Conductor Cover
Property |
Requirements |
Test Method |
Hardness Shore A |
65 |
ISO 868 |
Elongation |
200 % (min.) |
ASTM D 638 |
Tensile Strength
|
4 N/mm2 (min.) |
ASTM D 638 |
Tear Strength |
10 N/mm2 (min.) |
ASTM D 638 |
Dielectric Strength |
10 kV/mm (min.) |
ASTM D 2671 |
Volume Resistivity |
10 12 ohm cm (min.) |
ASTM D 2671 |