Heat Shrinkable Stress Control Tubing upto 36 kV

Heat Shrinkable Stress Control Tubing upto 36 kV

Enquire Now

Features

  • Electrical Stress Control at the end of the cable shielding
  • Suitable for underground buried Joint, Indoor & Outdoor termination
  • Continuous operation temperature: -40 C to 125 C
  • Meets the requirements of ENATS 09 13
  • Shrink Temperature: 120 C
  • Unlimited shelf life
  • UV Resistant
  • Shrink Ratio 3 : 1
Heat Shrinkable Stress Control Tubing upto 36 kV

Specifications

Dimension Chart for Heat Shrink Stress Control Tubing

Code As Supplied After Recovered
ø D1 (max.) ø D2 (max.) T (min.)
DSCT - / 26 10 26 10 2.1
DSCT - / 30 12 30 12 2.2
DSCT - / 35 15 35 15 2.3
DSCT - 40/16 40 16 2.4
DSCT - / 47 18 47 18 2.4
DSCT - / 55 21 55 21 2.4
DSCT - / 65 25 65 25 2.4
DSCT - / 75 30 75 30 2.4
Note: All dimensions are in mm

Technical Data for Heat Shrink Stress Control Tubing

Property Requirements Test Method
Physical
Tensile Strength 10 N/mm (min.) ASTM D 412 / ISO 37
Ultimate Elongation 200% (min.) ASTM D 412 / ISO 37
Water Absorption (25 C) 0.5% (max.) ASTM D 570
Thermal Ageing
Continuous Operating Temperature -55 C to +130 C IEC 216
Shrink Temperature 120 C (min.) IEC 216
Heat Shock (30 min. 200 C) No cracking / No flowing
Heat Ageing (168 hrs 120 C)
Tensile Strength 8.0 N/mm (min.) ASTM D 412 / ISO 37
Ultimate Elongation 100% (min.)
Low Temperature Flexibility (-20 C) No cracking ASTM D 2671
Electrical
Volume Resistivity 1 x 10 cm (min.) ASTM D 257 / IEC 93
Dielectric Constant 15 min. ASTM D 150 / IEC 250