DPMS/22 kV
Test Item of Pre Moulded Straight Through Joint as per IEC-60502-4 / IS:13573
Testing Items U o/U | 19/33 kV |
---|---|
A.C. withstand test | 58kV, 5min, no flashover |
Partial discharge test | 33kV<10pc (Max.) |
Thermal Cycles (63 cycles) | under 95-100° C 32kV |
Impulse voltage test | 125kV no flashover |
A.C. with stand test | 32kV, 15 min, no flashover |
Cable Cross Section (mm2) 22 kV |
22 kV, Joint, 1 Core | 22 kV, Joint, 3 Core | |
---|---|---|---|
DPMSS 22 - 1 X 50 | DPMS 22 - 3 X 50 | Enquire Now | |
DPMSS 22 - 1 X 70 | DPMS 22 - 3 X 70 | Enquire Now | |
DPMSS 22 - 1 X 95 | DPMS 22 - 3 X 95 | Enquire Now | |
DPMSS 22 - 1 X 120 | DPMS 22 - 3 X 120 | Enquire Now | |
DPMSS 22 - 1 X 150 | DPMS 22 - 3 X 150 | Enquire Now | |
DPMSS 22 - 1 X 185 | DPMS 22 - 3 X 185 | Enquire Now | |
DPMSS 22 - 1 X 240 | DPMS 22 - 3 X 240 | Enquire Now | |
DPMSS 22 - 1 X 300 | DPMS 22 - 3 X 300 | Enquire Now | |
DPMSS 22 - 1 X 400 | DPMS 22 - 3 X 400 | Enquire Now | |
DPMSS 22 - 1 X 500 | DPMS 22 - 3 X 500 | Enquire Now |