Download Brochure

Our Products  Accessories

Heat Shrinkable Anti Tracking Breakout
   

All Dimensions Are In mm
 
Features
  • Designed for medium voltage applications up to 36 KV
  • Shaped components to meet a variety of configuration requriements
  • Continuous operation temperature: -55° C to 120° C
Technical Data
Property Requirements Test Method
Tensile Strength 8N/mm2 (min.) ASTM D412, ESI 09-13
Elongation 200% (min) ASTM D412, ESI 09-13
Heat Aging
(500 hrs. at 1200 C)
   
Tensile Strength 7N/mm2 (min.) ASTM D412
Elongation 200% (min.) ASTM D412
Cold Temperature
Flex (-400 C)
No cracking ASTM D2671
Electrical    
Dielectric Strength
10 kV/mm (min.) ASTM D149, IEC 243
Volume Resistivity 1 x 1012 ohm-cm (min.) ASTM D257
Track Resistance Non-Tracking ASTM D2303
Chemical Resistance    
Tensile Strength 7N/mm2 (min.) ASTM D412
Elongation 200% (min.) ASTM D412
Dimension Chart
Code Expanded Recovered
Ø H (max.) Ø J(min.) Ø H (max.) Ø J(min.)
DIB - 1330 75 32 30 13 Enquiry
DIB - 2145 100 55 50 21 Enquiry
DIB - 2755 135 64 55 27 Enquiry

Our Products